GC1140 Insulated Inlet Poultry House Placement

Inlet Air Circulation Placement

 

Attic Inlet Capacity = House Width X House Length X 1.5 CFM/SF

# Attic Inlets per House = Attic Inlet Capacity / 1,669 CFM

Placement:

Place first and last inlet 20’ from endwall of house.

 

40’ Wide House

Alternate inlets either side of peak of the house

 

50’ Wide House

            Alternate inlets 2’ – 3’ from the peak of the house.

 

            60’ Wide House

            Alternate inlets 6-8’ from the peak of the house

 

Inlet spacing = (House Length – 40’) / (# Inlets +1)

            Example: 500 ft – 40ft = 460 ft

                            # inlets per house = 12

                            460 / (12 inlets per house +1) = 35.38ft

                            Inlet Spacing = 35 ft O.C.

Inlet Air Circulation Placement 2
poultry window 8 RetroAire Inlet decrease air or water leakage Custom sizes available Learn Made in the USA EcoDrive 300 Designed for expansion and contraction Perimeter gasket system to ensure a goo d seal between glass and outer frame to improve house tightness and decrease air or water leakage GC1140 Inlet Circulation 8 RetroAire Inlet EcoDrive 300 Designed for expansion and contraction Improves poultry house tightness and decreases air or water leakage Heavy-duty multi-walled construction of the panels offer high thermal resistance, giving excellent thermal insulating values while still allowing natural light to enter the house Perimeter gasket system to ensure a good seal between glass and outer frame to improve house tightness and decrease air or water leakage GC1140 Inlet Circulation Custom sizes available 8 RetroAire Inlet Perimeter gasket system to ensure a good seal between glass and outer frame to improve house tightness and decrease air or water leakage Custom sizes available EcoDrive 300 GC1140 Inlet Circulation Made in the USA Designed for expansion and contraction Poultry Division inlets Poultry Division inlets Learn Poultry Division inlets GC1140 Inlet Circulation